Commissioning
5.3 Procedure for commissioning via STARTER
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
123
5.3 Procedure for commissioning via STARTER
Basic procedure using STARTER
STARTER uses a sequence of dialog screens for entering the required drive unit data.
NOTICE
These dialog screens contain default settings, which you may have to change according to
your application and configuration.
This is intentional because
By taking time to consider what configuration data you enter, you can prevent
inconsistencies between the project data and drive unit data (identifiable in online mode).
5.3.1 Creating a project
Click the STARTER icon on your desktop or choose the following menu path in the Windows
start menu to call up STARTER: Start > Simatic > STEP 7 > STARTER.
The first time you run the software, the main screen (shown below) appears with the
following windows:
STARTER Getting Started Drive Commissioning
STARTER Project Wizard
The commissioning steps are listed below in numerical order.